Notifications
You must be signed in to change notification settings - Fork 6
Commit
This commit does not belong to any branch on this repository, and may belong to a fork outside of the repository.
draft of construction tolerances for built in place AguaClara plants
- Loading branch information
Showing
1 changed file
with
34 additions
and
2 deletions.
There are no files selected for viewing
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -1,6 +1,38 @@ | ||
.. _title_Construction_Tolerances: | ||
|
||
|
||
************* | ||
*********************** | ||
Construction Tolerances | ||
************* | ||
*********************** | ||
|
||
The construction tolerances are the allowable deviations from the design dimensions. The tolerances are specified in the table below. The tolerances are designed to ensure the hydraulic components of the plant will function as intended and to ensure the plant is aesthetically pleasing. | ||
|
||
.. _table_Construction_Tolerances: | ||
|
||
.. csv-table:: Construction Tolerances. | ||
:header: "Type", "Parameter", "English Units", "Metric Units" | ||
:align: left | ||
:widths: 80 20 | ||
:class: wraptable | ||
|
||
Elevation, Ledges and pipe supports, ±1/2 in., ±1.3 cm | ||
Elevation, Top of walls, ±1/2 in., ±1.3 cm | ||
Elevation, Top of weirs, ±1/8 in., ±0.3 cm | ||
Elevation, Top of slabs, ±3/8 in., ±1 cm | ||
Elevation, Tank bottoms, ±3/8 in., ±1 cm | ||
Cross-sectional, Width of walls, ±1/2 in., ±1.3 cm | ||
Cross-sectional, Width of beams, ±1/4 in., ±0.6 cm | ||
Cross-sectional, Width of columns, ±1/4 in., ±0.6 cm | ||
Cross-sectional, Thickness of slabs, ±1/4 in., ±0.6 cm | ||
Internal dimensions, Width and length of tanks, ±3/8 in., ±1 cm | ||
Alignment, Vertical alignment of walls, ±1/4 in., ±0.6 cm | ||
Alignment, Horizontal alignment of walls, ±1/4 in., ±0.6 cm | ||
Plumbness, Plumbness of columns, ±1/4 in. per 10 ft, ±0.6 cm per 3 meter | ||
Plumbness, Plumbness of walls, ±1/4 in. per 10 ft, ±0.6 cm per 3 meter | ||
Flatness, Flatness of slabs including tank bottoms, ±1/4 in. per 10 ft, ±0.6 cm per 3 meters | ||
Reinforcement, Location of reinforcing bars, ±1/2 in., ±1.3 cm | ||
Reinforcement, Cover to reinforcing bars, ±1/4 in., ±0.6 cm | ||
Surface Finish, Surface finish of formed concrete, No more than 1/8 in. deviation from a 10 ft straightedge, ±0.3 cm deviation from a 3 meter straightedge | ||
Pipes, Horizontal location of embedded horizontal or vertical pipes, ±1/2 in., ±1.3 cm | ||
Pipes, Vertical location of embedded horizontal pipes, ±1/4 in., ±0.6 cm | ||
|